Analog Input Specification | |
Input Signal | Thermocouple: 10 types (K,S,B,E,J,N,R,T,WRe526,WRe325) RTD-Resistance bulbs: 3 types(Pt100, CU50,CU100) Linear DC Voltage: (0-5VDC, 1-5VDC,0-10VDC) DC Current: (4-20mA, 0-10 mA) mV:0-20mV,0-60mV, 0-100mV, 0-500mV |
Accuracy |
|
Sampling Rate | ≤1 s |
Temperature Shift Coefficient | Standard value: 50PPM |
CMR Ratio | 85-110dB |
Input Independence | 0-5VDC and 1-5VDC input: 500KΩ 4-20mA input: 250 KΩ 0-10mA input: 500KΩ Other signal input :20MΩ |
Isolation | Isolated voltage between channels and ground: 1000VAC.Isolated voltage between channels:400VAC |
Input Error Action | Max, Min, Hold |
Power Supply Specification | |
Power supply | VAC: 100-240VAC, frequency: 47-63 HZ, max. power consumption: 5VA VDC: 24VDC,max power consumption: 5VA (please advise when order) |
Insulation | When power insulation to ground is higher than 1500VAC, leakage current: 10mA for one minute When power insulation to housing is higher than 1500VAC, leakage current: 10mA for one minute |
Output Specification | |
Aux. power supply | 24VDC, max.40mA for sensor and transmitters, up to 8 points built in |
Others | |
Processor | 32 bits, high performance and integrated ARM CPU |
Hardware guider | CPU inner integration for long time, stable and safe operation |
Hardware Clock | Adopt hardware real clock with high stability. Clock accuracy: +-5ppm. After power off, Li battery for continual power supply. The validity of battery is 30days. |
Data Memory | All data will be stored in FLASH memory, not need reserve battery in order to ensure that all the history data and configuration parameters will be not lost when power off. |
Comm. Port | Photoelectrical isolated RS485 communication interface |
Comm. Protocol | Standard MODBUS- RTU comm. protocol, can communicate with modern HMI and DCS directly. |
Printing Port | Photoelectrical isolated RS232C print port, Baudrate: 9600bps. Maximum print resolution:240dot/line |
Record Time | Record time =45daysx record interval÷ channel numbers . Can record 1 day data at least, also for 440 years at most |
Display | 7.0 inch, 320X240 TFT, Color LCD display |
Net Weight | Maximum 1kg |
Size | Dimension: 195mm*145mm*60.5mm Panel Flush Mounted |
Ambient | Working Temperature:0-50degC Relative humidity; 10%-85%( now dew) Transport and storage: -20-60℃ Relative humidity : 5%-95%(nodew) |
Multichannel Screen
The equipment uses RS485 communication connection acquisition card to achieve real-time recording, monitoring and query Cloud acquisition software, only NEED 4G wireless module communication, no wiring, easy to install! Mobile phone computer remote view data or graph, at the same time with SMS alarm function. Xiamen mitcheil automation co., Ltd. is a professional manufacturer of industrial instruments, advanced technology and CE, ROHS, ISO certification can ensure the quality. Our own production plant can ensure price advantage. At present, the company's trade scale is expanding day by day, customers all over the world, with good reputation has been the trust of customers at home and abroad, our enthusiasm hope: you and I hand in hand, create a better future!Packing: Put PC into bubble bag first, and then into carton Accessories: Manual, U disk Air freight: DHL, TNT and other expressMIC800G Selection of Paperless Recorder For example : MIC-808G-8-S3-P-U-T-N Meaning: Channel -------Input 8 Channels Relay Alarm Output-------8 alarm: NO ,30VDC/3A, 220VAC/3A Communication port-------Ethernet communication. Port, MODBUS-TCP/IP Printing--------RS232 printing port for mini printer, WH-E20 mini printer as default. Please advise the printer no. if the mini printer is customized. USB--------USB flash drive to download data to PC, free PC data analysis software offered TF function------TF card for extend data transferring automation. Power supply-------100-240VAC, 47-63HZ Communication Function | Code and Description | |||||||||||
Basic Code | MIC80 | MIC3000G Paperless Recorder | ||||||||||
Channel | 01G | One Channel | ||||||||||
02G | Two Channels | |||||||||||
… | …………… | |||||||||||
08G | Eight Channels | |||||||||||
Extendable Channel No. (RS485 Input) Analog Input only up to 8 channels when RS485 input | N | None | ||||||||||
E8 | Extendable 8 channels RS485 input | |||||||||||
E16 | Extendable 16 channels RS485 input | |||||||||||
E24 | Extendable 24 channels RS485 input | |||||||||||
Relay Alarm Output | N | None | ||||||||||
1 | 1 alarm: NO ,30VDC/3A, 220VAC/3A | |||||||||||
2 | 2 alarm: NO ,30VDC/3A, 220VAC/3A | |||||||||||
.... | ................................. | |||||||||||
8 | 8 alarm: NO ,30VDC/3A, 220VAC/3A | |||||||||||
Communication port | N | None | ||||||||||
S1 | RS485 communication. Port, MODBUS-RTU | |||||||||||
S2 | RS232 communication. Port, MODBUS-RTU | |||||||||||
S3 | Ethernet communication. Port, MODBUS-TCP/IP | |||||||||||
Printing | N | None | ||||||||||
P | RS232 printing port for mini printer, WH-E20 mini printer as default. Please advise the printer no. if the mini printer is customized. | |||||||||||
USB | U | USB flash drive to download data to PC, free PC data analysis software offered | ||||||||||
Flow Totalizer with Temperature and Pressure compensation; Math | N | None | ||||||||||
F | Flow totalizer accumulation with compensation; or Basic math: +, -, x, /, min, max, average | |||||||||||
Power supply | N | 100-240VAC, 47-63HZ | ||||||||||
D | DC24V | |||||||||||
Other |
Single channel Screen
History Circular Screen
History Trend Screen
Display screen on PC
Bar graph Screen